Embedded Feature and Option Module Parameters

Chapter 5

Univ

ersal

F

eedback

Regi

st

rati

on

91

Rgsn In 0 Filter
Registration Input 0 Filter
Configures a digital filter for the registration input 0. This filter can be used to reject
spurious noise. The filter works by waiting a programmed time before deciding that the
signal is valid. This waiting imposes a mandatory delay in the registration signal. The
filter delay is programmable in increments of 100 nanoseconds from 0 (or no delay) up
to 1500 nanoseconds.

Default:
Options:

0 = “0 ns”
0 = “0 ns”
1 = “100 ns”
2 = “200 ns”
3 = “300 ns”
4 = “400 ns”
5 = “500 ns”
6 = “600 ns”
7 = “700 ns”
8 = “800 ns”
9 = “900 ns”
10 = “1000 ns”
11 = “1100 ns”
12 = “1200 ns”
13 = “1300 ns”
14 = “1400 ns”
15 = “1500 ns”

RW Real

92

Rgsn In 1 Filter
Registration Input 1 Filter
Configures a digital filter for the registration input 1. This filter can be used to reject
spurious noise. The filter works by waiting a programmed time before deciding that the
signal is valid. This waiting imposes a mandatory delay in the registration signal. The
filter delay is programmable in increments of 100 nanoseconds from 0 (or no delay) up
to 1500 nanoseconds.

Default:
Options:

0 = “0 ns”
0 = “0 ns”
1 = “100 ns”
2 = “200 ns”
3 = “300 ns”
4 = “400 ns”
5 = “500 ns”
6 = “600 ns”
7 = “700 ns”
8 = “800 ns”
9 = “900 ns”
10 = “1000 ns”
11 = “1100 ns”
12 = “1200 ns”
13 = “1300 ns”
14 = “1400 ns”
15 = “1500 ns”

RW Real

93

Rgsn HmIn Filter
Registration Home Input Filter
Configures a digital filter for the home input. This filter can be used to reject spurious
noise. The filter works by waiting a programmed time before deciding that the signal is
valid. This waiting imposes a mandatory delay in the registration signal. The filter delay
is programmable in increments of 100 nanoseconds from 0 (or no delay) up to 1500
nanoseconds.

Default:
Options:

0 = “0 ns”
0 = “0 ns”
1 = “100 ns”
2 = “200 ns”
3 = “300 ns”
4 = “400 ns”
5 = “500 ns”
6 = “600 ns”
7 = “700 ns”
8 = “800 ns”
9 = “900 ns”
10 = “1000 ns”
11 = “1100 ns”
12 = “1200 ns”
13 = “1300 ns”
14 = “1400 ns”
15 = “1500 ns”

RW Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T