Troubleshooting
Chapter 6
11148
11248
11348
C1 Line Fuse L1
C2 Line Fuse L1
C3 Line Fuse L1
Non-Reset
Fault
Coast
The line fuse for Line n has blown.
• Check the fuse and replace if necessary.
• Verify that the line fuse wiring harness for line 1 is not damaged and
is connected to P7 on the converter gate firing board. Replace the
wiring harness if necessary.
• If this problem persists, replace the converter gate firing board.
11149
11249
11349
C1 Line Fuse L2
C2 Line Fuse L2
C3 Line Fuse L2
11150
11250
11350
C1 Line Fuse L3
C2 Line Fuse L3
C3 Line Fuse L3
11157
11257
11357
C1 BFuse Harness
C2 BFuse Harness
C3 BFuse Harness
Non-Reset
Fault
Coast
A bus fuse wiring harness connection loss has been detected.
• Check the bus fuse harness and replace if necessary.
• If this problem persists, replace the converter gate firing board.
11158
11258
11358
C1 BFuse Pos
C2 BFuse Pos
C3 BFuse Pos
Non-Reset
Fault
Coast
The DC+ bus fuse is blown.
• Check the DC+ bus fuse and wiring harness and replace if necessary.
• If this problem persists, replace the converter gate firing board.
11159
11259
11359
C1 BFuse Neg
C2 BFuse Neg
C3 BFuse Neg
Non-Reset
Fault
Coast
The DC- bus fuse is blown.
• Check the DC- bus fuse and wiring harness and replace if necessary.
• If this problem persists, replace the converter gate firing board.
11160
11260
11360
C1 Command Stop
C2 Command Stop
C3 Command Stop
Resettable
Fault
Coast
Y
The main control board has commanded the converter gate firing board
to stop due to an asymmetrical bus condition.
• Check the DC bus connections and wiring.
11161
11261
11361
C1 AC Line High
C2 AC Line High
C3 AC Line High
Resettable
Fault
Coast
The AC line voltage has exceeded 565V (for 400V class drives) or 815V
(for 600V class drives), which corresponds to the nominal bus voltage of
799V DC (for 400V class drives) or 1150V DC (for 600V class drives). This
fault is intended to protect the capacitor bank from an overvoltage
condition especially if a 400V class drive is inadvertently placed in a
600V system.
• Verify the incoming line voltage.
11162
11262
11362
C1 Line Loss
C2 Line Loss
C3 Line Loss
Resettable
Fault
Coast
Y
An AC line loss has occurred.
• Monitor the incoming AC line for low voltage or line power
interruption.
11163
11263
11363
C1 Fault Q Full
C2 Fault Q Full
C3 Fault Q Full
Resettable
Fault
Coast
The fault queue is full. There are at least three other faults in the queue.
• Troubleshooting and clearing the existing faults will make room for
additional faults in the queue (if any).
Event
No.
Fault/Alarm Text
Type
Fault
Action
Configuration
Parameter
Auto
Reset
Description/Action(s)