Port Verification

When connecting to select devices, such as PowerFlex 750-Series drives, the Port
Verification dialog box will display if device conflicts are found during the
connection process. These conflicts typically require resolution prior to
establishing the connection to the device.

The information and options available in this dialog box are detailed below:

Common Symptoms and
Corrective Actions

Drive does not Start from Start or Run Inputs wired to the terminal block.

Item

Description

Previous Setup

The device previously installed at the port identified.

Current Setup

The device currently installed at the port identified (if applicable).

(Device Not Found)

A message identifying the conflict at the identified port.

Changed

Indicates that the device previously installed at the port identified has been
removed or changed to a different device.

Not supported - Must remove device
before connection

Indicates that the device currently installed at the port identified has a
firmware revision that is not compatible with the drive. The drive must be flash
updated to be able to use this device or the device must be removed from the
port before a connection can be made.

Not functioning - Must remove
device before connection

Indicates that the device currently installed at the port identified is not
functioning. The device must be removed from the port before a connection can
be made.

Invalid Duplicate - Must remove
device before connection

Indicates that the device currently installed at the port identified is already
installed at another port for the device to which you are attempting to connect
and the device cannot support the number of devices installed. The duplicate
device must be removed from the port before a connection can be made.

Requires Configuration

Indicates that the device installed at the port identified requires configuration
before a connection can be made.

Accept All

Accepts all configuration changes and continues the device connection process.

Cancel

Cancels the device connection process.

Cause(s)

Indication

Corrective Action

Drive is Faulted

Flashing red
status light

Clear fault.
Press Stop
Cycle power
“Clear Faults” on the HIM Diagnostic

menu.

Incorrect input wiring. See Installation Instructions,
publication 750-IN001, for wiring examples.
2 wire control requires Run, Run Forward, Run

Reverse or Jog input.

3 wire control requires Start and Stop inputs.
Verify 24 Volt Common is connected to Digital

Input Common.

None

Wire inputs correctly.

Incorrect digital input programming.
Mutually exclusive choices have been made (i.e.,

Jog and Jog Forward).

2 wire and 3 wire programming may be

conflicting.

Start configured without a Stop configured.

None

Configure input function.

Flashing yellow
status light and
“DigIn Cnfg B”
or
“DigIn Cnfg C”
indication on LCD
HIM.
P936 [Drive Status
2] shows type 2
alarm(s).

Resolve input function conflicts.

Terminal block does not have control.

None

Check P324 [Logic Mask].