h. In the Path field, enter the drive name to configure the communication
path of the message instruction to that drive.
In this case, the drive name in the Logix I/O tree is “_DriveName.”
i. The value for Total Life returns in the double integer (DINT) data
format.
The raw data = Hours x 100. Divide by 100 to get the Total Life in
hours. The CPT block (see
) performs this division.
Figure 83 - Predictive Main Group Parameters (Port 0)
4.
Use a message instruction to retrieve the [Elapsed Life] value for the
cabinet fan from converter 1. [Elapsed Life] data returns with a floating
point (Real) data format. See
.
Figure 84 - Message Instruction for Elapsed Life Parameter