Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 317

Rockwell Automation Publication 750-PM001J-EN-P - October 2014
317
Troubleshooting
Chapter 6
102
NVS Not Blank
Resettable
Fault
Coast
Internal data error.
103
PwrDn NVS Incomp
Resettable
Fault
Coast
Internal data error.
104
Pwr Brd Checksum
Non-Reset
Fault
The checksum read from the non-volatile storage does not match the
checksum calculated. Data set to default value.
106
Incompat MCB-PB
Non-Reset
Fault
Coast
The main control board did not recognize the power structure. Flash
with newer Application version.
107
Replaced MCB-PB
Resettable
Fault
Coast
The main control board was moved to a different power structure. Data
set to default values.
108
Anlg Cal Chksum
Non-Reset
Fault
Coast
The checksum read from the analog calibration data does not match the
checksum calculated. Replace main control board.
110
Ivld Pwr Bd Data
Non-Reset
Fault
Coast
Power structure data invalid.
• Verify ribbon cable connection between the main control board and
the power interface board.
• Replace power interface board.
111
PwrBd Invalid ID
Non-Reset
Fault
Coast
Power structure ID invalid.
• Verify ribbon cable connection between the main control board and
the power interface board.
• Replace power interface board.
112
PwrBd App MinVer
Resettable
Fault
Coast
Power structure needs newer Application version. Flash with newer
Application version.
113
Tracking DataErr
Resettable
Fault
Coast
Internal data error.
115
PwrDn Table Full
Resettable
Fault
Coast
Internal data error.
116
PwrDnEntry2Large
Resettable
Fault
Coast
Internal data error.
117
PwrDn Data Chksm
Resettable
Fault
Coast
Internal data error.
118
PwrBd PwrDn Chks
Resettable
Fault
Coast
Internal data error.
124
App ID Changed
Resettable
Fault
Coast
Application Firmware changed. Verify Application version.
125
Using Backup App
Resettable
Fault
Coast
Application did not flash correctly. Reflash.
134
Start On PowerUp
Alarm 1
When P345 [Start At PowerUp] is enabled, an alarm will be set for the
time programmed in P346 [PowerUp Delay].
137
Ext Prechrg Err
Configurable
The seal contact on the external precharge contactor has opened (as
signalled by P190 [DI Prchrg Seal]) while the drive was running (PWM
was active).
138
Precharge Open
Resettable
Fault
Coast
[Prchrg Control]
[DI Prchrg Seal]
[DI Precharge]
The internal precharge was commanded to open while the drive was
running (PWM was active). The internal fault latch will be automatically
cleared when PWM is disabled.
141
Autn Enc Angle
Resettable
Fault
Coast
P78 [Encdrlss AngComp] is out of range.
142
Autn Spd Rstrct
Resettable
Fault
Coast
Frequency limit settings are preventing the drive from reaching a
suitable speed during an Inertia Tune test.
143
Autotune CurReg
Resettable
Fault
Coast
Calculated values for P96 [VCL Cur Reg Kp] and/or P97 [VCL Cur Reg Ki]
are out of range.
144
Autotune Inertia
Resettable
Fault
Coast
Results from the Inertia Tune test out of range for P76 [Total Inertia].
145
Autotune Travel
Resettable
Fault
Coast
When P77 [Inertia Test Lmt] is set, the Inertia Tune test was prevented
from reaching a suitable speed to run the test.
Event
No.
Fault/Alarm Text
Type
Fault
Action
Configuration
Parameter
Auto
Reset
Description/Action(s)