Him indication, Fault display screen, Manually clearing faults – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 309: Him indication manually clearing faults
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
309
Troubleshooting
Chapter 6
HIM Indication
Fault Display Screen
The pop-up Fault Display screen automatically appears when a fault condition
for the Host Drive or any connected peripheral is detected. The pop-up Fault
Display screen flashes to alert that a fault condition exists. This screen displays
the:
•
Fault and Alarm Display Codes on page 312
•
Fault description
•
Elapsed time (in hh:mm:ss format) from fault detection
Figure 4 - Pop-Up/Flashing Fault Display Screen
Soft Key Functions
Single Function Key
Manually Clearing Faults
Label
Name
Description
ESC
Escape
Reverts back to the previous screen without clearing the fault.
CLR
Clear
Removes the pop-up Fault Display screen from the display and clears
the fault.
Key
Name
Description
Stop
Removes the pop-up Fault Display screen from the display and clears the
fault.
Stopped
0.00 Hz
AUTO
Fault Code 81
Port 1 DPI Loss
Elapsed Time 01:26:37
ESC
F
CLR
– – FAULTED – –
Step
Key(s)
1. Press the “Clear” soft key to acknowledge the fault. The fault information will be removed so that
you can use the HIM.
2. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3. After corrective action has been taken, clear the fault by one of these methods:
Press Stop (if running the drive will stop)
Cycle drive power
Select the “Clear” soft key on the HIM Diagnostic folder Faults menu.
CLR