Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 204

204
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 3
Drive Port 0 Parameters
Fil
e
Gr
ou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta T
ype
APPLIC
AT
ION
S
Va
ri
ab
le
B
oo
st
1535
VB Config
Variable Boost Configuration
RO
16-bit
Integer
Controls the variable boost function.
Bit 0 “VB Enable” – Enables the variable boost voltage function.
Bit 1 “Current Rate” – The current rate trigger condition is defined by the level set in P1550 [VB Cur Thresh] with a hysteresis band of P1549 [VB Current Hyst]. The
slope of P1548 [VB Current Rate] is set to either default falling edge or rising edge by Bit 2 “Rising Edge.” If these trigger conditions are met, P1536 [VB Status] Bit 3
“Current Trig” is set.
Bit 2 “Rising Edge” – The current rate trigger condition is defined by the level set in P1550 [VB Cur Thresh] with a hysteresis band of 1549 [VB Current Hyst]. The
slope of P1548 [VB Current Rate] is set to either default falling edge or rising edge by Bit 2 “Rising Edge.” If these trigger conditions are met, P1536 [VB Status] Bit 3
“Current Trig” is set.
Bit 3 “Flux Level” – Sets the flux trigger condition defined by the level of P1545 [VB Flux Thresh]. If P1547 [VB Filt Flux Cur] is greater than or equal to P1545 [VB
Flux Thresh], P1536 [VB Status] Bit 4 “Flux Trigger” is set.
Bit 4 “Minimum Freq” – Sets the minimum frequency trigger source derived from P1 [Output Frequency] and is enabled by setting P1535 [VB Config] Bit 4
“Minimum Freq.” If P1 [Output Frequency] is less than or equal to P1544 [VB Min Freq], P1536 [VB Status] Bit 5 “Freq Trigger” is set.
1536
VB Status
Variable Boost Status
RO
16-bit
Integer
Status bits for the variable boost function.
Bit 0 “VB Enabled” – The variable boost voltage function is enabled.
Bit 1 “VB Timer” – P1538 [VB Time] has expired.
Bit 2 “Triggered” – Indicates that a trigger function has been enabled by 1535 [VB Config].
Bit 3 “Current Trig” – This trigger condition is defined by P1550 [VB Cur Thresh] with a hysteresis band of P1549 [VB Current Hyst]. The slope of P1548 [VB Current
Rate] is set to either default falling edge or rising edge by P1535 [VB Config] Bit 2 “Rising Edge.” If these trigger conditions are met, this bit is set.
Bit 4 “Flux Trigger” – This trigger event is enabled by P1535 [VB Config] Bit 3 “Flux Level.” The trigger condition is defined by the level P1545 [VB Flux Thresh]. If
P1547 [VB Filt Flux Cur] is greater than or equal to P1545 [VB Flux Thresh], P1536 [VB Status] Bit 4 “Flux Trigger” is set.
Bit 5 “Freq Trigger” – This trigger event is enabled when P1 [Output Frequency] is less than or equal to P1544 [VB Min Freq].
Bit 6 “Max Boost” – This trigger event is enabled when P1537 [VB Voltage] reaches P1540 [VB Maximum] before any of the other trigger events cause P1537 [VB
Voltage] to ramp down.
Bit 7 “Hold Freq” – Output frequency is being held at P1543 [VB Frequency].
1537
VB Voltage
Variable Boost Voltage
Displays the output value of the voltage-axis intercept of the V/Hz curve.
When the variable boost function is enabled, the value of [VB Voltage] is ramped up/
down according to the settings of the variable boost function when the drive is running.
This parameter is equal to P60 [Start Acc Boost] and P61 [Run Boost] when the drive is
stopped or when P1535 [VB Config] Bit 0 “VB Enable” = 0.
Units:
Default:
Min/Max:
V AC
0.0
0.0 / 460.0
RO
Real
Options
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Minimum F
req
Fl
ux
L
eve
l
Ris
in
g E
dge
Cu
rr
en
t R
at
e
VB E
nable
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Disabled
1 = Enabled
Options
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Ho
ld
Fre
q
M
ax B
oost
Fr
eq T
rigger
Fl
ux T
rigger
Cu
rr
en
t T
rig
Tr
igger
ed
VB T
im
er
VB E
nabled
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Condition False
1 = Condition True