Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 260

260
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 5
Embedded Feature and Option Module Parameters
Fil
e
Gr
ou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta T
ype
22-S
eries I/O
Mo
to
r PT
C
40
PTC Cfg
Positive Temperature Coefficient Configuration
Sets the action that will be taken when the PTC is not Ok.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.
Default:
Options:
0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop”
5 = “Flt CL Stop”
RW 32-bit
Integer
41
PTC Sts
Positive Temperature Coefficient Status
RO
16-bit
Integer
Status of the PTC.
Bit 0 “PTC Ok” – PTC is OK
Bit 1 “PTC Short” – PTC is Shorted
Bit 2 “Over Temp” – PTC is indicating over temperature
42
PTC Raw Value
Positive Temperature Coefficient Raw Value
Displays the value of the PTC.
Units:
Default:
Min/Max:
Volt
0
0 / 10
RO
Real
Options
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Res
er
ved
Ov
er
T
em
p
PT
C Sh
or
t
PT
C O
k
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Condition False
1 = Condition True
Fi
le
Grou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta T
ype
22-S
eries I/O
An
al
og In
put
s
45
Anlg In Type
Analog Input Type
RO
16-bit
Integer
Status of the analog input mode set by the option jumpers.
46
Anlg In Sqrt
Analog Input Square Root
RW 16-bit
Integer
Enables/disables the square root function for each input.
Options
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Analog 1
Analog 0
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Voltage Mode
1 = Current Mode
Options
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Re
ser
ve
d
Analog 1
Analog 0
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Square Root Disabled
1 = Square Root Enabled