7 operationenabled, Operationenabled, Status – Lenze 8400 StateLine User Manual
Page 91: 4device control (dctrl)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
91
4
Device control (DCTRL)
4.2
Device state machine and device states
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.7
OperationEnabled
The drive controller is in this device status if the controller inhibit is deactivated and no error
("Trouble" or "TroubleQSP") has occurred.
If the operation is enabled and the magnetisation in case of sensorless vector control (SLVC) has
been completed, the motor follows the setpoint determined by the active application.
Depending on certain conditions, a status change takes place based on the "OperationEnabled"
device status.
Related topics:
wCANControl/wMCIControl control words
"DRV-RDY" LED
"DRV-ERR" LED
Display in status word 1 (
)
Bit 11
Bit 10
Bit 9
Bit 8
OFF
OperationEnabled
0
1
0
1
Change condition
Changeover to the device status
Control bit "EnableOperation" of a control channel = "0"
OR terminal RFR = LOW level (controller inhibit).
Control bit "SwitchOn" of a control channel = "0".
Undervoltage in the DC bus.
)
Error with error response "Trouble" occurs.
Error with error response "TroubleQSP" occurs.