C01123 | sync window, C01124 | sync correction width, C01138 | l_transient 1-4: function – Lenze 8400 StateLine User Manual
Page 782: C01123, C01124, 15 parameter reference
15
Parameter reference
15.2
Parameter list | C01123
782
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01123
C01124
C01138
Parameter | Name:
C01123 | Sync window
Data type: UNSIGNED_16
Index: 23452
d
= 5B9C
h
From version 03.00.00
Time slot for monitoring the synchronisation signal or the phase position
• The synchronisation signal or the current phase position must be within this time slot around the corresponding
expected value (
).
• With the setting "1000 μs" there will be no monitoring.
Synchronisation of the internal time base
Setting range
(min. value | unit | max. value)
Lenze setting
0
μs
10000 100 μs
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01124 | Sync correction width
Data type: UNSIGNED_8
Index: 23451
d
= 5B9B
h
From version 03.00.00
Correction increment for device synchronisation
• If the cycle times of the synchronisation signal differs and phase-locken loop (PLL) differ from each other, this
setting defines the measure the phase-locking loop is reset with.
• If synchronisation is not reached, select a higher correction constant.
• The optimum setting depends on quartz precision and must be determined empirically if required.
Synchronisation of the internal time base
Selection list
(Lenze setting printed in bold)
1 100ns
2 200ns
3 300ns
4 400ns
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01138 | L_Transient 1-4: Function
Data type: UNSIGNED_8
Index: 23437
d
= 5B8D
h
From version 04.00.00
Selection of edge evaluation
Selection list
0 High edge
1 Low edge
2 High and low edge
Subcodes
Lenze setting
Info
C01138/1
0: High edge
: Function
C01138/2
0: High edge
: Function
C01138/3
0: High edge
: Function
C01138/4
0: High edge
: Function
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1