Synchronisation of the internal time base
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13
Synchronisation of the internal time base
In a drive system, synchronising the internal time bases of all controllers involved makes sense
because cyclic process data should be processed synchronously in all drives.
• One of the following signal sources can be used for automatic synchronisation of the internal
time base of the controller:
• CAN bus ("CAN on board")
• MCI sync signal of a plugged-in communication module
(EtherCAT, PROFINET or Powerlink)
Short overview of the parameters for the synchronisation of the internal time base:
Sync signal source
The synchronisation signal source can be selected in
. As a general rule, only one source can
be used to synchronise the internal time base.
Sync cycle time setpoint
Time after which the internal phase-locking loop (PLL) anticipates the synchronisation signals. The
according to the cycle of the synchronisation source selected in
Example: For the CAN bus, 2 ms has been selected as interval between two synchronisation signals.
If the CAN bus is to be used as synchronisation source, a cycle time setpoint of 2000 μs must be
Parameter
Info
Lenze setting
Value Unit
CAN Sync instant of transmission
- μs
Sync instant of reception
- μs
Sync signal source
Off
Sync cycle time setpoint
1000 μs
Sync phase position
0 μs
Sync window
100 μs
Sync correction width
300 ns
Highlighted in grey = display parameter
Note!
• Only integer multiples of 1000 μs can be set in
.
• Intelligent communication modules usually define the cycle time setpoint derived
from the bus cycle. In this case, a manual change is not possible.