5motor control (mctrl) – Lenze 8400 StateLine User Manual
Page 113
![background image](/manuals/566309/113/background.png)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
113
5
Motor control (MCTRL)
5.1
Motor selection/Motor data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Principal sequence of the motor parameter identification
1. The motor stator resistance (
) is measured.
2. The inverter error characteristic is measured.
3. The motor stator leakage inductance (
) is measured.
4. The V/f base frequency (
) is calculated.
5. The slip compensation (
) is calculated.
6. The V
min
) is detected.
7. Only for asynchronous motors:
The motor magnetising inductance (
) and the motor rotor resistance (
measured.
The motor magnetising current (
) is measured.
From version 12.00.00:
8. If
- bit 4 = "0" (Lenze setting):
The current controller and field controller parameters are calculated. (See
table
.)
9. If
- bit 5 = "1":
The speed controller parameters are calculated. (See
table
.)
10. If
- bit 6 = "1":
Other controller parameters are calculated. (See
table
.)
Selection of the identification mode
From version 10.00.00 onwards
, two identification modes are available in
• "1: Basic identification" (previous mode)
• Only for asynchronous motors
• Duration approx. 30 s
• "2: extended identification"
• Stands out due to increased accuracy of the determined motor parameters.
• Also supports synchronous motors and asynchronous motors with a power of more than 11
kW.
• Duration approx. 80 s
Tip!
In the Lenze setting, a setting of "0: automatic" is selected in
. This setting ensures
that the controller automatically selects the optimum procedure for motor parameter
identification.