Basic drive functions (MCK)
8.4
Holding brake control
404
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
bMBrakeApplied
BOOL
(from version 11.00.00)
Input for status detection via switching contacts at the brake
• Only effective if bit 5 in
is set to "1".
FALSE Brake is released.
TRUE Brake is applied.
Identifier
Data type
Value/meaning
bMBrakeReleaseOut
BOOL
Trigger signal for switching element holding brake control via a digital output
• Use bit 0 under
to activate inverted switching element triggering.
FALSE Apply brake.
TRUE Release brake.
bMBrakeReleased
BOOL
"Brake released" status signal considering the brake release time
• When the holding brake is triggered to close, bMBrakeReleased is immediately set
to FALSE even if the brake closing time has not yet elapsed!
TRUE Brake released (after the brake release time has expired).
Stop!
The digital outputs are not suitable for the "direct" control of a holding brake!
• Connect the digital output connected to the trigger signal bMBrakeReleaseOut with a
relay or power contactor which switches the brake supply.
• When a power contactor is used, the response and release time of the earth contact is
added to the response and release time of the brake. Both times must also be
considered for parameterising the closing and opening time of the holding brake