C00122 | initial value motor overload (i·xt), C00123 | device utilisation threshold (ixt), C00129 | brake resistance value – Lenze 8400 StateLine User Manual
Page 624: C00130 | rated power - brake resistor, C00123, C00129, C00130, C00122, Ce parameterised in, 15 parameter reference
15
Parameter reference
15.2
Parameter list | C00122
624
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00122
C00123
C00129
C00130
Parameter | Name:
C00122 | Initial value motor overload (I²xt)
Data type: UNSIGNED_16
Index: 24453
d
= 5F85
h
From version 12.00.00
The thermal motor load displayed in
is pre-initialised with the value set here when the device is connected
to the mains.
• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.
• Recommended setting for operation according to UL: 50.00 %
Motor overload monitoring (I2xt)
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00122/1
0.00 %
Initial value motor overload (I²xt)
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00123 | Device utilisation threshold (Ixt)
Data type: INTEGER_16
Index: 24452
d
= 5F84
h
Operating threshold for the "OC5: Device overload (Ixt)" error message
• The response for reaching the threshold can be selected in
.
• The current device utilisation is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
200.00 100.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00129 | Brake resistance value
Data type: UNSIGNED_16
Index: 24446
d
= 5F7E
h
From version 03.00.00
Resistance value of the connected brake resistor
• The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
Ohm
500.0 39.0 Ohm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00130 | Rated power - brake resistor
Data type: UNSIGNED_16
Index: 24445
d
= 5F7D
h
From version 03.00.00
Rated power of the connected brake resistor
• The value to be entered can be obtained from the nameplate of the brake resistor.
Setting range
(min. value | unit | max. value)
Lenze setting
0
W
65535 100 W
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1