C00338 | l_arithmetik_1: function, C00339 | l_arithmetik_2: function, C00338 – Lenze 8400 StateLine User Manual
Page 661: 15 parameter reference
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
661
15
Parameter reference
15.2
Parameter list | C00338
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00338
C00339
Parameter | Name:
C00338 | L_Arithmetik_1: Function
Data type: UNSIGNED_8
Index: 24237
d
= 5EAD
h
FB: Selection of internal arithmetics
Selection list
(Lenze setting printed in bold)
0 Out = In1
1 Out = In1 + In2
2 nOut_a = nIn1_a - nIn2_a
3 Out = (In1 * In2) / 100%
4 nOut_a = (nIn1_a * 1%) / |nIn2_a|
5 nOut_a = (nIn1_a * 100%) / (100% -
nIn2_a)
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00339 | L_Arithmetik_2: Function
Data type: UNSIGNED_8
Index: 24236
d
= 5EAC
h
From version 11.00.00
FB: Selection of internal arithmetics
Selection list
(Lenze setting printed in bold)
0 nOut_a = nIn1_a
1 nOut_a = nIn1_a + nIn2_a
2 nOut_a = nIn1_a - nIn2_a
3 nOut_a = (nIn1_a * nIn2_a) / 100%
4 nOut_a = (nIn1_a * 1%) / |nIn2_a|
5 nOut_a = (nIn1_a * 100%) / (100% -
nIn2_a)
Read access Write access CINH PLC STOP No transfer COM MOT