C00169 | logbook setting, C00170 | current error, C00170 – Lenze 8400 StateLine User Manual
Page 641: C00169, Yed in, 15 parameter reference
![background image](/manuals/566309/641/background.png)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
641
15
Parameter reference
15.2
Parameter list | C00169
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00169
C00170
C00171
Parameter | Name:
C00169 | Logbook setting
Data type: UNSIGNED_16
Index: 24406
d
= 5F56
h
Configuration which message types are to be logged in the logbook.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF 0x067E (decimal: 1662)
Value is bit-coded: ( = bit set)
Bit 0
Reserved
Bit 1 Log entry: Fault
Bit 2 Log entry: Trouble
Bit 3 Log entry: TroubleQuickstop
Bit 4 Log entry: WarningLocked
Bit 5 Log entry: Warning
Bit 6 Log entry: Information
Bit 7
Reserved
Bit 8
Reserved
Bit 9 Activation: Error counter
Bit 10 Activation: Log line refresh
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00170 | Current error
Data type: UNSIGNED_32
Index: 24405
d
= 5F55
h
Display of the internal error number of the currently pending error
Display range
(min. value | unit | max. value)
0
4294967295
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00171 | Logbook access index
Data type: UNSIGNED_8
Index: 24404
d
= 5F54
h
This code is for device-internal use only and must not be written to by the user!