C00905 | motor phase direction of rotation, C00909 | speed limitation, C00910 | frequency limitation – Lenze 8400 StateLine User Manual
Page 763: C00909/1, C00909/2, C00910/1, C00910/2, C00909/x, C00909, C000910
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
763
15
Parameter reference
15.2
Parameter list | C00905
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00905
C00909
C00910
Parameter | Name:
C00905 | Motor phase direction of rotation
Data type: UNSIGNED_8
Index: 23670
d
= 5C76
h
From version 04.00.00
To correct such misconnected motor phases, the rotating field of the controller's output can be reversed by selecting
"1: Inverted". In this case, a phase will be reversed at the output of the inverter.
Note:
Up to and including version 11.00.00
, this function may only be activated for the following motor control types:
• V/f characteristic control (VFCplus)
• Energy-saving V/f characteristic control (VFCplusEco)
For all other motor control types, this function must not be activated because the set control mode would not work
in that case!
From version 12.00.00
, this function may be activated for all motor control types with the exception of the ones for
synchronous motor.
The activation of this function does not affect the control types for synchronous motor since these control types
require an in-phase connection of the synchronous motor.
Selection list
(Lenze setting printed in bold)
0 not inverted
1 inverted
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00909 | Speed limitation
Data type: INTEGER_16
Index: 23666
d
= 5C72
h
Max. positive/negative speed for all motor control modes
Setting range
(min. value | unit | max. value)
0.00
%
175.00
Subcodes
Lenze setting
Info
C00909/1
120.00 %
Max. pos. speed
C00909/2
120.00 %
Max. neg. speed
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00910 | Frequency limitation
Data type: UNSIGNED_16
Index: 23665
d
= 5C71
h
Max. positive/negative output frequency for all motor control modes
Setting range
(min. value | unit | max. value)
0
Hz
1300
Subcodes
Lenze setting
Info
C00910/1
1000 Hz
Max. pos. output frequency
C00910/2
1000 Hz
Max. neg. output frequency
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1