Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
615
15
Parameter reference
15.2
Parameter list | C00065
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00065
C00066
C00070
C00071
Parameter | Name:
C00065 | Supply voltage 24V
Data type: INTEGER_16
Index: 24510
d
= 5FBE
h
Display of the 24V supply voltage for the supply of the control electronics
Note:
The 24 V supply for the control electronics is either provided by an external supply or by the controller itself if it is
connected to the mains voltage.
Display range
(min. value | unit | max. value)
0.0
V
3276.7
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load, sensorlessly determined using a motor model
• If the value displayed here exceeds "100.00 %", the error message "OC6: Thermal motor overload (I2xt)" is output
is executed (default setting: "Warning").
Motor overload monitoring (I2xt)
Display range
(min. value | unit | max. value)
0.00
%
199.99
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00070 | Vp speed controller
Data type: UNSIGNED_16
Index: 24505
d
= 5FB9
h
Amplification factor Vp of the speed controller for different motor control modes
Setting range
(min. value | unit | max. value)
0.00
600.00
Subcodes
Lenze setting
Info
C00070/1
15.00
: Vp speed controller
C00070/2
6.00
Reserved
C00070/3
3.00
: Vp speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00071 | Ti speed controller
Data type: UNSIGNED_16
Index: 24504
d
= 5FB8
h
Reset time Ti of the speed controller for different motor control modes
Setting range
(min. value | unit | max. value)
0.0
ms
6000.0
Subcodes
Lenze setting
Info
C00071/1
100.0 ms
: Ti speed controller
C00071/2
50.0 ms
Reserved
C00071/3
100.0 ms
: Ti speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10