C00011 | appl.: reference speed, C00012 | accel. time - main setpoint, C00013 | decel. time - main setpoint – Lenze 8400 StateLine User Manual
Page 606: C00015 | vfc: v/f base frequency, C00011, C00012, C00013, C00015, Rence speed set in, Up to the traversing speed set in
15
Parameter reference
15.2
Parameter list | C00011
606
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00011
C00012
C00013
C00015
Parameter | Name:
C00011 | Appl.: Reference speed
Data type: UNSIGNED_16
Index: 24564
d
= 5FF4
h
Setting the reference speed
• In the controller, all speed-related signals are processed to one reference variable in percent.
• Set a reference speed here that corresponds to 100 %.
• The frequency that corresponds to the set reference speed is displayed in
Note:
This is not a maximum limitation!
All values in percent in the controller may be in a range of 0 ... 199.99 %.
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
60000 1500 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00012 | Accel. time - main setpoint
Data type: UNSIGNED_32
Index: 24563
d
= 5FF3
h
FB: Acceleration time of the ramp generator for the main speed setpoint
• Generally, this ramp generator is used for all speed-controlled technology applications.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 2.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00013 | Decel. time - main setpoint
Data type: UNSIGNED_32
Index: 24562
d
= 5FF2
h
FB: Deceleration time of the ramp generator for the main speed setpoint
• Generally, this ramp generator is used for all speed-controlled technology applications.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 2.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00015 | VFC: V/f base frequency
Data type: UNSIGNED_16
Index: 24560
d
= 5FF0
h
V/f base frequency for V/f characteristic control (
• The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on,
the motor voltage remains constant, the speed increases and the maximum torque decreases.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
7.5
Hz
2600.0 50.0 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10