C02289/1, C02289/2, C02289/3 – Lenze 8400 StateLine User Manual
Page 808: C02289/4, C02290/1, C02290/2, C02290/3, C02290/4, C02291/1, C02291/2
15
Parameter reference
15.2
Parameter list | C02289
808
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02289
C02290
C02291
Parameter | Name:
C02289 | LS_WriteParamList: VFC-ECO: Minimum voltage U/f
Data type: INTEGER_16
Index: 22286
d
= 570E
h
From version 12.00.00 onwards
: Parameter values (1st value ... 4th value) for optional
Setting range
(min. value | unit | max. value)
20.00
%
100.00
Subcodes
Lenze setting
Info
C02289/1
20.00 %
: c977_val1
C02289/2
20.00 %
: c977_val2
C02289/3
20.00 %
: c977_val3
C02289/4
20.00 %
: c977_val4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C02290 | LS_WriteParamList: VFC-ECO: Voltage reduction ramp
Data type: UNSIGNED_8
Index: 22285
d
= 570D
h
From version 12.00.00 onwards
: Parameter values (1st value ... 4th value) for optional
Setting range
(min. value | unit | max. value)
0.0
s
5.0
Subcodes
Lenze setting
Info
C02290/1
0.8 s
: c982_val1
C02290/2
0.8 s
: c982_val2
C02290/3
0.8 s
: c982_val3
C02290/4
0.8 s
: c982_val4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C02291 | LS_WriteParamList: SLVC: Field current controller gain
Data type: INTEGER_16
Index: 22284
d
= 570C
h
From version 12.00.00 onwards
: Parameter values (1st value ... 4th value) for optional
Setting range
(min. value | unit | max. value)
0.00
%
20.00
Subcodes
Lenze setting
Info
C02291/1
0.50 %
: c985_val1
C02291/2
0.50 %
: c985_val2
C02291/3
0.50 %
: c985_val3
C02291/4
0.50 %
: c985_val4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100