Oc12, Oc12: i2xt brake resistor overload, Oc12: i2xt overload brake resistor – Lenze 8400 StateLine User Manual
Page 458: Xx.0123.00058, Xx.0123.00059, Xx.0123.00060, Xx.0123.00061, Xx.0123.00065, 9diagnostics & error management
![background image](/manuals/566309/458/background.png)
9
Diagnostics & error management
9.9
Error messages of the operating system
458
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Id3: CINH identification [xx.0123.00058]
Id4: Resistor identification error [xx.0123.00059]
Id7: Motor control does not match motor data [xx.0123.00060]
Id8: Speed encoder has not been set [xx.0123.00061]
oC12: I2xt overload - brake resistor [xx.0123.00065]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected controller inhibit during the
motor data identification.
• This cancels the identification process. The Lenze
setting of the motor data is used.
• Do not set controller inhibit during the motor data
identification.
• Do not execute any device function which may
activate controller inhibit.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that an error has occurred in
the calculation of the motor cable resistance.
• The parameters for cable cross-section and cable
length are implausible.
Enter sensible values for cable cross-section and motor
cable length.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
At controller enable, the device has detected that the
cannot control the
motor type set.
• Example: Motor nameplate data for an asynchronous
motor have been entered; however, a motor control
type for a synchronous motor is set in
.
Note:
Since the "VFCplus" control types are able to control
every motor to a certain extent, this error message will
never occur here.
Enter correct motor nameplate data and set a matching
motor control type in
:
• Motor nameplate data asynchronous motor motor
control type must be ASM, SLVC or VFCplus servo
control.
• Motor nameplate data synchronous motor motor
control type must be PSM, SLPSM or VFCplus servo
control.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
When being In controller enable status, the device has
detected that a motor control type with feedback has
, but no speed sensor has been set in
Set the speed sensor in
.
Note: The error can only be reset if the settings in
and
match.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Too frequent and too long braking processes.
Check drive dimensioning.