C01351
Parameter | Name:
C01351 | ACDrive: Control word
Data type: UNSIGNED_16
Index: 23224
d
= 5AB8
h
From version 13.00.00
Display of the "AC Drive Profile" control word for the controller
• Detailed information on the "AC Drive Profile" can be found in the EtherNet/IP™ communication manual.
Actuating drive speed (AC Drive Profile)
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 Run Forward
Relationships between Run1 and Run2 and trigger
events can be found in the chapter "
".
Bit 1 Run Backward
Bit 2 Fault Reset
0->1 ≡ Reset error
0 ≡ No response
Bit 3
Reserved
Bit 4
Reserved
Bit 5 NetCtrl
Run/Stop control:
0 ≡ via local setting in the device or terminal
1 ≡ via fieldbus (e.g. by the scanner)
Bit 6 NetRef
Reference speed/reference torque:
0 ≡ via local setting in the device or terminal
1 ≡ via fieldbus (e.g. by the scanner)
Bit 7
Reserved
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Subcodes
Info
C01351/1
ACDrive: Control word
Read access Write access CINH PLC STOP No transfer COM MOT