C00448
C00449
Parameter | Name:
C00448 | DigOut decoupling value
Data type: UNSIGNED_16
Index: 24127
d
= 5E3F
h
From version 04.00.00
Definition of the value the digital output terminals are to have in the decoupled state.
• Bit set = HIGH level
Configuring exception handling of the output terminals
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF 0x0000 (decimal: 0)
Value is bit-coded: ( = bit set)
Bit 0 Relay_ON
Bit 1 DigOut1_ON
Bit 2
Reserved
Bit 3
Reserved
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00449 | FreqInxx_dnOut_p
Data type: INTEGER_32
Index: 24126
d
= 5E3E
h
From version 06.00.00
Output of the encoder position of the DI1/DI2 frequency input
Display range
(min. value | unit | max. value)
-2147483647
Incr.
2147483647
Subcodes
Info
C00449/1
FreqIn12_dnOut_p
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1