Ps10: invalid memory module binding, Error messag, Xx.0145.00014 – Lenze 8400 StateLine User Manual
Page 466: Xx.0145.00024, Xx.0145.00025, Xx.0144.00008, Xx.0144.00009, Xx.0144.00010, 9diagnostics & error management
9
Diagnostics & error management
9.9
Error messages of the operating system
466
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS08: Par. device invalid [xx.0144.00008]
PS09: Par. format invalid [xx.0144.00009]
PS10: Memory module binding invalid [xx.0144.00010]
dF14: SW-HW invalid [xx.0145.00014]
dF18: BU RCOM error [xx.0145.00024]
dF25: CU RCOM error [xx.0145.00025]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The parameter set in the device is invalid.
• The error occurs while loading the parameter set.
• One code in the device is incorrect.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The code format is invalid.
• The error occurs while loading the parameter set.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device personalisation is active: The binding ID of the
memory module does not comply with the binding ID of
the controller.
• Use memory module/controller with matching
binding IDs.
• Contact machine manufacturer.
Note:
It is not possible for Lenze to modify a replacement
device via special accesses in such a way that it
cooperates with a personalised memory module.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.