Oh3: motor temperature (x106) triggered, Error m, Sible temperature. the – Lenze 8400 StateLine User Manual
Page 454: Oh1: overtemperature, Heatsink, Oh4: heatsink, Temp.. > switch-off temp °c, Xx.0119.00001, Xx.0119.00015, Xx.0119.00000
9
Diagnostics & error management
9.9
Error messages of the operating system
454
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Su04: CU insufficiently supplied [xx.0111.00004]
Su06: Mains input overload [xx.0111.00006]
oH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]
oH1: Heatsink overtemperature [xx.0119.00001]
oH3: Motor temperature (X106) triggered [xx.0119.00015]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
After switching on the device, the 24V supply voltage for
the control electronics is too low (100 ms after switch-on
U is < 19V).
• The current supply voltage is displayed in
With internal supply voltage via the power electronics,
the controller must be replaced.
With external supply voltage, check the correct
connection and/or the stability of the supply voltage.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
In order to protect the device from overload, the
following device outputs have a hardware detection in
the mains input: 7.5 kW, 11 kW, 15 kW, 30 kW, 37 kW, 45
kW.
In case of the error message "Su06", this hardware
detection has responded.
• Check whether all mains phases are connected (a 2-
phase supply may be existent).
• Provide for sufficient cooling of the device.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The heatsink temperature now only differs by 5 °C from
the shutdown temperature of the motor.
Prevent further heating, i.e. reduce motor load or set
controller inhibit so that the heatsink can cool down
again.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The heatsink temperature is higher than the fixed limit
temperature (90 ° C).
Maybe the ambient temperature of the controller is too
high or the fan or its ventilation slots are dirty.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
• If required, clean or replace the fan.
• Provide for sufficient cooling of the device.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.