FC02: Maximum speed for Fchop [xx.0123.00095]
oC14: Direct-axis current controller limitation [xx.0123.00096]
oC15: Cross current controller limitation [xx.0123.00097]
oC16: Torque controller limitation [xx.0123.00098]
FC03: Field controller limitation [xx.0123.00099]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Maximum speed for chopper frequency has been
reached.
• The maximum speed has been exceeded depending
on the switching frequency.
Select the correct maximum speed as a function of the
switching frequency.
Motor control: Determine speed limits
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Direct-axis current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Cross current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
• Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Actuator limitation according to speed controller.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
• Observe load requirements.
• Correct dimensioning or reduce setpoint from the
field weakening range if necessary.