Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
623
15
Parameter reference
15.2
Parameter list | C00115
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00115
C00118
C00120
Parameter | Name:
C00115 | DI1| DI2: Function
Data type: UNSIGNED_8
Index: 24460
d
= 5F8C
h
Function assignment of the digital terminals DI1 and DI2
Selection list
Info
0 DI1=In1 | DI2=In2
DI1 = digital input
DI2 = digital input
1 DI1=FreqIn12 | DI2=In2
DI1 = 1-track frequency input
DI2 = digital input
2 (DI1/DI2)=FreqIn12 (2-track)
DI1 and DI2 = 2-track frequency input
3 (DI1/DI2=+-)=FreqIn12
DI1 = 1-track frequency input
DI2 = specification of direction
4 DI1=CountIn1 | DI2=In2
DI1 = counter input
DI2 = digital input
Subcodes
Lenze setting
Info
C00115/1
0: DI1=In1 | DI2=In2
Function assignment of DI1 and DI2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00118 | DigOutX: Inversion
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
The polarity of each digital output of the device can be inverted via this bit field.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF 0x00 (decimal: 0)
Value is bit-coded: ( = bit set)
Info
Bit 0 Relay inverted
Relay inversion
Bit 1 DO1 inverted
Inversion of digital output 1
Bit 2
Reserved
Bit 3
Reserved
Bit 4
Reserved
Bit 5
Reserved
Bit 6
Reserved
Bit 7
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00120 | Setting of motor overload (I²xt)
Data type: INTEGER_16
Index: 24455
d
= 5F87
h
Operating threshold for the "OC6: Motor overload (I²xt)" error message
• The response for reaching the threshold can be selected in
.
• The current thermal motor load is displayed in
Motor overload monitoring (I2xt)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
250.00 100.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100