Ck16: time overflow manual control, Error m, Xx.0184.00005 – Lenze 8400 StateLine User Manual
Page 468: Xx.0184.00064, Xx.0145.00052, Xx.0400.00009, Xx.0400.00016, 9diagnostics & error management

9
Diagnostics & error management
9.9
Error messages of the operating system
468
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
dF52: BuCcr error [xx.0145.00052]
Ck15: Error status sign. brake [xx.0184.00005]
Ck16: Time overflow manual operation [xx.0184.00064]
dH09: EEPROM power section [xx.0400.00009]
dH10: Fan failure [xx.0400.00016]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Mains switching
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: The status monitoring of the holding brake control
has tripped.
• Check configuration of the bMBrakeApplied input for
status detection of the brake (via a switching contact
at the brake).
• Check wiring/function of the switching contact.
• Adapt waiting time (
).
• Deactivate status monitoring (via bit 5 in
).
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
PC manual control: The connection monitoring has
tripped.
• The online connection between the PC and the
controller has been interrupted for a longer period of
time than the timeout set in
• Check communication link between PC and
controller.
• Check voltage supply/function of the controller.
• Adjust the timeout (
).
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device fan has failed.
Possible causes:
• The short-circuit check of the fan connection has
tripped.
• The speed monitoring of the fan has tripped.
• Check the fan for short-circuit.
• Clean the fan.