Parameter | Name:
C00633 | L_NSet_1: Min.SkipFrq.
Data type: INTEGER_16
Index: 23942
d
= 5D86
h
Minimum limit values for the speed blocking zones
• Selection of the minimum limit values for the blocking zones in which the speed must not be constant.
Setting range
(min. value | unit | max. value)
0.00
%
199.99
Subcodes
Lenze setting
Info
C00633/1
0.00 %
: Blocking speed1 min
C00633/2
0.00 %
: Blocking speed2 min
C00633/3
0.00 %
: Blocking speed3 min
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00634 | L_NSet_1: wState
Data type: UNSIGNED_16
Index: 23941
d
= 5D85
h
FB: Bit coded status display
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 No blocking zone active
1 ≡ No blocking zone set for constant speeds
Bit 1 Blocking zone 1 active
1 ≡ Suppression of constant speed characteristics within
the limits of blocking zone 1
Bit 2 Blocking zone 2 active
1 ≡ Suppression of constant speed characteristics within
the limits of blocking zone 2
Bit 3 Blocking zone 3 active
1 ≡ Suppression of constant speed characteristics within
the limits of blocking zone 3
Bit 4 Jog in blocking zone
1 ≡ A ramp is used to keep the speed setpoint within a
speed blocking zone
Bit 5 MaxLimit active
1 ≡ Speed setpoint is at the maximum speed limit
Bit 6 MinLimit active
1 ≡ Speed setpoint is at the minimum speed limit
Bit 7
Reserved
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT