C00185 | autofailreset remaining time, C00186 | max. number of autofailreset processes, C00187 | current autofailreset processes – Lenze 8400 StateLine User Manual
Page 645: C00188 | autofailreset configuration, C00185, C00186, C00187, C00188, 15 parameter reference
![background image](/manuals/566309/645/background.png)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
645
15
Parameter reference
15.2
Parameter list | C00185
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00185
C00186
C00187
C00188
Parameter | Name:
C00185 | AutoFailReset remaining time
Data type: UNSIGNED_16
Index: 24390
d
= 5F46
h
Display of the residual runtime of the "AutoFailReset" function
Display range
(min. value | unit | max. value)
0
s
600
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00186 | Max. number of AutoFailReset processes
Data type: UNSIGNED_8
Index: 24389
d
= 5F45
h
Maximum number of "AutoFailReset" procedures
Setting range
(min. value | unit | max. value)
Lenze setting
1
16 4
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00187 | Current AutoFailReset processes
Data type: UNSIGNED_8
Index: 24388
d
= 5F44
h
Data of the current number of "AutoFailReset" procedures
Display range
(min. value | unit | max. value)
0
16
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00188 | AutoFailReset configuration
Data type: UNSIGNED_8
Index: 24387
d
= 5F43
h
Setting which error messages are to be reset automatically.
Selection list
(Lenze setting printed in bold)
Info
0 Off
No automatic error message reset
1 Fault + TroubleQSP
Error messages with the response "Fault" and
"TroubleQSP" are reset automatically
2 WarningLocked
Error messages with the response "WarningLocked" are
reset automatically
3 All locking
All "locking" error messages are reset automatically
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1