C00055 | actual values, C00056 | torque, C00057 | maximum torque – Lenze 8400 StateLine User Manual
Page 613: C00058 | output frequency, C00058, C00056/2, C00057, Is dire, C00056/1, C00055/1
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
613
15
Parameter reference
15.2
Parameter list | C00055
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00055
C00056
C00057
C00058
Parameter | Name:
C00055 | Actual values
Data type: INTEGER_16
Index: 24520
d
= 5FC8
h
Note:
When a single-track feedback has been selected for the HTL encoder (
= 1 or 3), the sign of the actual speed
value is created from the sign of the speed setpoint. In C00055/1, a positive speed is always displayed.
Display range
(min. value | unit | max. value)
-32767
rpm
32767
Subcodes
Info
C00055/1
Actual value - HTL encoder FreqIn12
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00056 | Torque
Data type: INTEGER_32
Index: 24519
d
= 5FC7
h
Display of the current torque
Display range
(min. value | unit | max. value)
-65000.00
Nm
65000.00
Subcodes
Info
C00056/1
Torque demand
• Only in case of sensorless vector control (
C00056/2
Actual torque value
• Estimated actual torque for all motor control modes.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00057 | Maximum torque
Data type: UNSIGNED_32
Index: 24518
d
= 5FC6
h
Display of the maximum torque to be generated by the motor
• The maximum torque to be generated by the motor depends on various factors, e.g. on Imax in motor mode
(
) and the motor type used.
Display range
(min. value | unit | max. value)
0.00
Nm
65000.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00058 | Output frequency
Data type: INTEGER_32
Index: 24517
d
= 5FC5
h
Display of the current output frequency
Display range
(min. value | unit | max. value)
-1300.00
Hz
1300.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100