Xx.0131.00006, Xx.0131.00007, Xx.0127.00002 – Lenze 8400 StateLine User Manual
Page 462: Xx.0127.00015, Xx.0131.00000, 9diagnostics & error management
![background image](/manuals/566309/462/background.png)
9
Diagnostics & error management
9.9
Error messages of the operating system
462
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CE04: MCI communication error [xx.0127.00002]
CE0F: MCI control word [xx.0127.00015]
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00006]
CA07: CAN bus warning [xx.0131.00007]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Communication error with extension module in slot 1.
• Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes with the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: A faulty CAN telegram has been detected.
• Check wiring and bus terminating resistor.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Incorrect transmission or reception of
more than 96 CAN telegrams.
• The current number of incorrectly transmitted CAN
• The current number of incorrectly received CAN
• The current CAN error status is displayed in
.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).