Parameter reference
15.2
Parameter list | C00350
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00350
C00351
C00352
Parameter | Name:
C00350 | CAN node address
Data type: UNSIGNED_8
Index: 24225
d
= 5EA1
h
Setting of the node address via parameters
• The node address can only be parameterised if the node address "0" is set via the DIP switches.
• A change in the node address will not be effective until a CAN Reset Node is performed.
Setting range
(min. value | unit | max. value)
Lenze setting
1
127 1
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00351 | CAN baud rate
Data type: UNSIGNED_8
Index: 24224
d
= 5EA0
h
Setting of the baud rate via parameters
• The baud rate can only be parameterised if the baud rate "0" is set via the DIP switches.
• A change in the baud rate will not be effective until a CAN Reset Node is performed.
Selection list
(Lenze setting printed in bold)
0 500 kbps
1 250 kbps
2 125 kbps
3 50 kbps
4 1000 kbps
5 20 kbps
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00352 | CAN slave/master
Data type: UNSIGNED_8
Index: 24223
d
= 5E9F
h
The drive starts as CAN master after mains switching if a value of "1" has been entered and saved here.
Selection list
(Lenze setting printed in bold)
0 Slave
1 Master
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1