C00806 | l_mpot_1: use, C00820 | l_digitallogic_1: function, C00821 | l_digitallogic_1: truth table – Lenze 8400 StateLine User Manual
Page 743: C00806, Ctivation is possible via, Or via, Are or'd, He logic operation is selected in, C00820, C00821/1
![background image](/manuals/566309/743/background.png)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
743
15
Parameter reference
15.2
Parameter list | C00806
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00806
C00820
C00821
Parameter | Name:
C00806 | L_MPot_1: Use
Data type: UNSIGNED_8
Index: 23769
d
= 5CD9
h
FB: Use of the motor potentiometer
Selection list
(Lenze setting printed in bold)
Info
0 No
The motor potentiometer is not used.
• The analog value applied to the nIn_a input is looped
through without any changes to the nOut_a output.
1 Yes
The motor potentiometer is used.
• The analog value applied at the nIn_a input is led via
the motor potentiometer and provided at the nOut_a
output.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00820 | L_DigitalLogic_1: Function
Data type: UNSIGNED_8
Index: 23755
d
= 5CCB
h
FB: Selection of the internal logic function
Selection list
(Lenze setting printed in bold)
Info
0 bOut = 0
Constant value "FALSE"
1 bOut = 1
Constant value "TRUE"
2 bOut = bIn1 AND bIn2 AND bIn3
AND operation
3 bOut = bIn1 OR bIn2 OR bIn3
OR operation
4 bOut = f (truth table)
The truth table parameterised in
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00821 | L_DigitalLogic_1: Truth table
Data type: UNSIGNED_8
Index: 23754
d
= 5CCA
h
FB: Parameterisation of the truth table
Selection list
0 False
1 True
Subcodes
Lenze setting
Info
C00821/1
0: FALSE
: bIn3...bIn1=0 0 0
C00821/2
0: FALSE
: bIn3...bIn1=0 0 1
C00821/3
0: FALSE
: bIn3...bIn1=0 1 0
C00821/4
0: FALSE
: bIn3...bIn1=0 1 1
C00821/5
0: FALSE
: bIn3...bIn1=1 0 0
C00821/6
0: FALSE
: bIn3...bIn1=1 0 1
C00821/7
0: FALSE
: bIn3...bIn1=1 1 0
C00821/8
0: FALSE
: bIn3...bIn1=1 1 1
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1