4 remedies for undesired drive behaviour, Remedies for undesired drive behaviour, 5motor control (mctrl) – Lenze 8400 StateLine User Manual
Page 143
![background image](/manuals/566309/143/background.png)
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
143
5
Motor control (MCTRL)
5.4
V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.4
Remedies for undesired drive behaviour
Drive behaviour
Remedy
Inadequate smooth running at low speeds, especially in
the case of operation with a long motor cable
Automatic motor data identification ( 111)
Problems in case of high starting duty (great mass
inertia)
Adapting the Vmin boost ( 135)
Drive does not follow the speed setpoint.
The current controller intervenes in the set field
frequency to limit the controller output current to the
maximum current (C0022, C0023). Therefore:
• Prolong acceleration/deceleration times:
Accel. time - main setpoint
: Decel. time - main setpoint
• Consider a sufficient magnetising time of the motor.
Depending on the motor power, the magnetising
time amounts to 0.1 ... 0.2 s.
• Increase the maximally permissible current:
: Imax in motor mode
: Imax in generator mode)
For operation without speed feedback (
= 6):
Insufficient speed constancy at high load (setpoint and
motor speed are not proportional anymore)
• Increase slip compensation (
Important: Unstable drive due to overcompensation!
• With cyclic load impulses (e. g. centrifugal pump), a
smooth motor characteristic is achieved by smaller
values in
(possibly negative values).
Note: The slip compensation is only active for operation
without speed feedback.
"Clamp operation active" error message (oC11):
Controller cannot follow dynamic processes, i.e. too
short acceleration/deceleration times in terms of load
ratios.
• Increase the gain of the I
max
controller (
• Reduce the reset time of the I
max
controller
(
• Prolong the acceleration time (
)
• Prolong the deceleration time (
Motor stalling in the field weakening range
(adaptation especially required for small machines)
• Reduce the override point of field weakening
(
)
• If motor power < inverter power:
max
= 2 I
rated motor
• Reduce dynamic performance of setpoint generation