C00469 | keypad: fct. stop key, C00470 | ls_parfree_b, C00471 | ls_parfree – Lenze 8400 StateLine User Manual
Page 691: C00469, 15 parameter reference
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
691
15
Parameter reference
15.2
Parameter list | C00469
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00469
C00470
C00471
Parameter | Name:
C00469 | Keypad: Fct. STOP key
Data type: INTEGER_32
Index: 24106
d
= 5E2A
h
Selection of the function for the STOP key on the keypad
Selection list
(Lenze setting printed in bold)
Info
0 No response
STOP key does not have any function
1 Inhibit controller
STOP key sets controller inhibit in the drive
2 Activate quick stop
STOP key sets quick stop in the drive
4 Inhibit controller and reset error
From version 14.00.00
STOP key sets controller inhibit in the drive. An error
reset is carried out at the same time.
5 Activate quick stop and reset error
From version 14.00.00
STOP key sets quick stop in the drive. An error reset is
carried out at the same time.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00470 | LS_ParFree_b
Data type: UNSIGNED_8
Index: 24105
d
= 5E29
h
SB: Setting of the signal level to be output
Selection list
0 False
1 True
Subcodes
Lenze setting
Info
C00470/1
0: FALSE
Signal level for output bPar1 ... bPar16
C00470/...
C00470/16
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00471 | LS_ParFree
Data type: UNSIGNED_16
Index: 24104
d
= 5E28
h
SB: Setting of the words to be output
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Bit 0 Bit0
... ...
Bit 15 Bit15
Subcodes
Lenze setting
Info
C00471/1
0x0000
Value for output wPar1 ... wPar4
C00471/...
C00471/4
Read access Write access CINH PLC STOP No transfer COM MOT