I-1017, The parameterised time, I-1018 – Lenze 8400 StateLine User Manual
Page 549: 11 system bus "can on board
Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14
549
11
System bus "CAN on board"
11.11
Implemented CANopen objects | I-1017
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1017
Time interval for sending the heartbeat telegram to the consumer(s).
• The parameterised time is rounded down to an integer multiple of 5 ms.
• The heartbeat telegram is automatically sent as soon as a time > 0 ms is entered. In this case,
the "node guarding" monitoring function is deactivated.
• This object relates to code
.
I-1018
Index:
I-1017
Name:
Producer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Producer heartbeat time
0
0
ms
65535 rw
U16
Index:
I-1018
Name:
Identity object
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
see below
0
4294967295 ro
U32
1: Vendor ID
2: Product code
3: Revision number
4: Serial number
Subindex
Meaning
1
Manufacturer's identification number
• The identification number allocated to Lenze by the organisation "CAN in
Automation e. V." is "0x0000003B".
2
Product code
0x84001 8400 BaseLine C
0x84002 8400 StateLine C
0x84003 8400 HighLine C
0x84004 8400 TopLine C
3
Main and subversion of firmware
4
Serial number