APPLICATIONS OF Σ-SERIES PRODUCTS
3.1.3 Restricting Torque
60
• Using /CLT Signal
This section describes how to use contact output signal /CLT as a torque limit output sig-
nal.
SGDB SERVOPACK
I/O power
supply
Photocoupler Output
Per output:
Maximum operation
voltage: 30 VDC
Maximum output
current: 50 mA DC
/CLT−
/CLT+
Output → /CLT 1CN-*1
Torque Limit Output
For Speed/Torque
Control and
Position Control
This signal indicates whether motor output torque (current) is being restricted.
ON status: The circuit between 1CN-*1
and 1CN-*2
is closed.
1CN-*1
is at low level.
Motor output torque is being restricted.
(Internal torque reference is greater than the
preset value.)
OFF status: The circuit between 1CN-*1
and 1CN-*2
is open.
1CN-*1
is at high level.
Motor output torque is not being restricted.
(Internal torque reference is equal to or below
the preset value.)
Preset Value: Cn-08 (TLMTF)
Cn-09 (TLMTR)
Cn-18 (CLMIF) : P-CL input only
Cn-19 (CLMIR) : N-CL input only
Cn-2D
Output Signal Selection
Factory
Setting: 210
For Speed/Torque Control
and Position Control
Specifies the terminal to which /CLT is to be output.
Setting
Output terminals (1CN-)
g
*1
*2
1s place = 3
25
26
10s place = 3
27
28
100s place = 3
29
30
3
100s place = 3
10s place = 3
1s place = 3
(1CN-25, 26)
(1CN-27, 28)
(1CN-29, 30)
Torque
detection
/CLT