2 wiring for noise control – Yaskawa SGDB User Manual
Page 156

APPLICATIONS OF Σ-SERIES PRODUCTS
3.8.2 Wiring for Noise Control
144
MCCB or Fuse for Each Power Capacity
SERVOPACK
Type
Power Capacity Per
SERVOPACK (kVA)
(see note 1)
Current Capacity Per MCCB or
Fuse (A)
(see note 2)
SGDB-03ADj
0.65
5
SGDB-05ADj
1.1
5
SGDB-07ADj
1.5
8
SGDB-10ADj
2.0
8
SGDB-15ADj
2.5
10
SGDB-20ADj
4.0
12
SGDB-30ADj
5.0
18
SGDB-44ADj
7.0
24
SGDB-50ADj
7.5
28
SGDB-60ADj
12.5
32
SGDB-75ADj
15.0
41
SGDB-1AADj
19.0
60
SGDB-1EADj
30.0
80
Note
1) Power capacity at rated load
2) Operating characteristics (25°C): 2 seconds or more for 200%, 0.01 second or more for
700%
3) A fast-operating fuse cannot be used because the SERVOPACK power supply is a ca-
pacitor input type. A fast-operating fuse may blow out when the power is turned ON.
3.8.2 Wiring for Noise Control
J
Example of Wiring for Noise Control
This SERVOPACK uses high-speed switching elements in the main circuit. It may re-
ceive “switching noise” from these high-speed switching elements if wiring or grounding
around the SERVOPACK is not appropriate. To prevent this, always wire and ground the
SERVOPACK correctly.
This SERVOPACK has a built-in microprocessor (CPU). To protect the microprocessor
from external noise, install a noise filter in place.
3