Yaskawa SGDB User Manual
Page 569
563
Category
Re-
mar
ks
Factory
Setting
Upper
Limit
Lower
Limit
Unit
Name
Code
Parame-
ter No.
Cn-06
EMGTRQ
Emergency stop
torque
%
0
800
800
Cn-13
TCRFGN
Torque reference gain
0.1 V/
100%
10
100
30
Cn-14
TCRLMT
Speed limit for torque
control
min
−1
0
10000
10000
Sequence Re-
l
d
Cn-2D
OUTSEL
Output signal selection *1
110
666
210
q
lated
Constants
Cn-0B
TGONLV
Zero-speed level
min
−1
1
10000
20
Constants
Cn-29
ZCLVL
Zero clamp level
min
−1
0
10000
10
Cn-22
VCMPLV
Speed coincidence
signal output range
min
−1
0
100
10
Cn-1B
COINLV
Positioning completion
range
reference
unit
0
250
7
Cn-1E
OVERLV
Overflow
256 refer-
ence unit
1
32767
1024
Cn-12
BRKTIM
Time delay from brake
reference until servo
OFF
10 ms
0
50
0
Cn-15
BRKSPD
Speed level for brake
reference output dur-
ing motor operation
min
−1
0
10000
100
Cn-16
BRKWAI
Output timing of brake
reference during motor
operation
10 ms
10
100
50
Other
C
Cn-10
JOGSPD
Jog speed
min
−1
0
10000
500
Constants
Cn-1F
SPEED1
1st speed (contact in-
put speed control)
min
−1
0
10000
100
Cn-20
SPEED2
2nd speed (contact in-
put speed control)
min
−1
0
10000
200
Cn-21
SPEED3
3rd speed (contact in-
put speed control)
min
−1
0
10000
300
Cn-2C
PGPWR
PG power supply volt-
age change
0.1 mV
52000
58000
52500
: Parameters must be set and checked before turning the motor power ON.
Note
*1 Refer to page 568.
*2 After changing the setting, always turn the power OFF, then ON. This makes the new
setting valid.
*3 Automatically set by auto tuning function
*4 To use soft start function, always set both Cn-07 and Cn-23.
*5 6.0kW or less : 4, 7.5kW : 8, 11.0 to 15.0kW : 16
C