INSPECTION, MAINTENANCE, AND TROUBLESHOOTING

6.2.1 Troubleshooting Problems with Alarm Display cont.

526

J

CPF00

Display and Outputs

Digital Operator

Di l

d

Alarm Output

g

p

Display and

Alarm Name

Alarm Code Output

Alarm Output

Alarm Name

ALO1

ALO2

ALO3

p

CPF00

Digital operator

transmission

error 1

Not specified

Note

This alarm is not stored in alarm trace-back function memory.

Status When Alarm Occurred

A

,

B

,

C

,

D

At power ON. Digital op-

erator connected before

SERVOPACK power

turned ON.

Digital operator con-

nected to SERVOPACK

while power turned ON.

A

,

B

,

C

,

D

Cause

Remedy

A

Cable defective or poor contact between

digital operator and SERVOPACK.

• Check connector connections.
• Replace cable.

B

Malfunction due to external noise

Separate digital operator and cable from

noise source.

C

Digital operator defective

Replace digital operator.

D

SERVOPACK defective

Replace SERVOPACK.

6