4 using speed coincidence output signal, Output → /v-cmp 1cn-25 – Yaskawa SGDB User Manual
Page 146

APPLICATIONS OF Σ-SERIES PRODUCTS
3.7.4 Using Speed Coincidence Output Signal
134
3.7.4 Using Speed Coincidence Output Signal
This section describes how to wire and use contact output signal “speed coincidence out-
put (/V-CMP).” This signal is output to indicate that actual motor speed matches a refer-
ence speed. The host controller uses this signal as an interlock.
SERVOPACK
I/O power supply
Photocoupler Output
Per output:
Maximum operation voltage:
30 VDC
Maximum output current: 50
mADC
/V-CMP+
/V-CMP−
Output → /V-CMP 1CN-25
Speed Coincidence Output
For Speed Control
Only
This output signal indicates that actual motor
speed matches the input speed reference during
speed control.
ON
status:
Circuit between 1CN-25 and 1CN-26 is
closed.
1CN-25 is at low level.
Actual motor speed matches the speed
reference (speed difference is below the
preset value).
OFF
status:
Circuit between 1CN-25 and 1CN-26 is
open.
1CN-25 is at high level.
Actual motor speed does not match the
speed reference (speed difference is
greater than the preset value).
Preset value: Cn-22 (speed coincidence signal output width)
Use the following parameter to output the /V-CMP signal.
Cn-2D
OUTSEL
Output signal
selection
Setting Range:
110 to 666
Factory
Setting:
210
This parameter is used to specify a function signal as the 1CN output signal.
1s place
Select the 1CN-25 and 1CN-26 (/COIN, /V-CMP) functions.
10s place
Select the 1CN-27 and 1CN-28 (/TGON) functions.
100s place
Select the 1CN-29 and 1CN-30 (/S-RDY) functions.
3
Motor
speed
Reference
speed
/V-CMP is output within