beautypg.com

Yaskawa SGDB User Manual

Page 40

background image

BASIC USES OF Σ-SERIES PRODUCTS

2.2.5 Installing the SERVOPACK cont.

28

Installation method:

When installing multiple SERVOPACKs side by side in a control panel, observe the fol-
lowing installation method:

Fan

50 mm or more

Fan

30 mm or more

10 mm or more

Fan

50 mm or more

a) Install SERVOPACK perpendicular to the wall so that the front panel (digital operator

mounted face) faces outward.

b) Provide sufficient space around each SERVOPACK to allow cooling by fan and natu-

ral convection.

c) When installing SERVOPACKs side by side, provide at least 10 mm space between

them and at least 50 mm space above and below them as shown in the figure above.
Install cooling fans above the SERVOPACKs to prevent the temperature around each
SERVOPACK from increasing excessively and also to maintain the temperature in-
side the control panel evenly.

d) Maintain the following conditions inside the control panel:

• Ambient temperature for SERVOPACK: 0 to 55°C

• Humidity: 90%RH or less

• Vibration: 4.9 m/s

2

• Condensation and freezing: None

• Ambient temperature to ensure long-term reliability: 45°C or less

2