6.2 Troubleshooting

509

J

A.40

Display and Outputs

Digital Operator

Di l

d

Alarm Output

g

p

Display and

Alarm Name

Alarm Code Output

Alarm Output

Alarm Name

ALO1

ALO2

ALO3

p

A.40

Main circuit

voltage error

detection.

OFF

OFF

ON

OFF

OFF: Output transistor is OFF
ON: Output transistor is ON

Status When Alarm Occurred

Occurred when the control

power turned ON.

E

Occurred approximately

0.6 second after the main

circuit power turned ON.

A, D

At power ON

A, B, C, D

Cause

Remedy

A

The power supply voltage is not within the

range of specifications.

Check power supply.

B

Load exceeds capacity of the regenerative

unit.

Check specifications of load inertia and

overhanging load.

C

Regenerative transistor is abnormal.

Replace SERVOPACK.

D

• Rectifying diode defective.
• Fuse blown.
• Inrush current-limited resistor discon-

nected.

p

E

SERVOPACK defective.