To ensure that values are downloaded only if the electronic signature is verified, you must
secure the graphic objects separately. To do this, use one of these methods:

Turn off the Enter key, by using the /E parameter with the Display command. For
details about the Display command, see the FactoryTalk View Site Edition Help.

Use display keys to set the Page Up, Ctrl+Page Up, Page Down, and Ctrl+Page Down
keys to do nothing. For details about setting up display keys, see page 18-20.

Tracking changes using FactoryTalk Diagnostics

The operations initiated by the signature button are logged to FactoryTalk Diagnostics,
and can be viewed in the Diagnostics List or Diagnostics Viewer.

The logged information includes user name, old value, new value, operator’s comments,
and name of the person approving the change.

For information about logging system activity, see Chapter 15, Logging system activity.