5–36

• •

Switching the Active and Secondary servers in a redundant pair, see page 14-19.

Enabling or disabling, suppressing or unsuppressing, or acknowledging FactoryTalk
alarms, see Chapter 12, Setting up FactoryTalk alarms.

In the Security Settings dialog box, you might also see actions for other FactoryTalk
products, for example, RSLinx Enterprise. For details about product-specific actions, see
the product documentation.

To do this

In this component or tool

You need these security permissions

Open an existing networkdistributed, network
station, or localstation application and view
its contents.

FactoryTalk View Studio

FactoryTalk View SE
Administration Console

Common Read

Common List Children

Run an existing network distributed, network
station, or localstation application and write to
tags.

FactoryTalk View SE Client

Common Read

Common List Children

Tag Write Value

At least one security code (A to P) set up
in the Runtime Security editor. For
details, see page 5-11.

The Common actions Read and List Children allow basic access to a network or local system. To increase access, add
security permission, as shown in the remainder of this table.

Open an existing application and modify its
properties.

FactoryTalk View Studio

FactoryTalk View SE
Administration Console

Common Read

Common List Children

Common Write

Create an application and modify its
properties.

Add new areas, HMI servers, data servers, or

Tag Alarm and Event Server

s to an

application.

FactoryTalk View Studio

Common Read

Common List Children

Common Create Children

Common Write

Modify the properties of existing HMI
servers, data servers, or

Tag Alarm and

Event Server

s.

FactoryTalk View Studio

Common Read

Common List Children

Common Write

Create or modify HMI project components,
for example, graphic displays or derived tags
files.

Add HMI project components into an
application.

FactoryTalk View Studio

Common Read

Common List Children

Common Create Children

Common Write

Common Delete