beautypg.com

Alarm class, Alarm class – 12 – Rockwell Automation FactoryTalk View Site Edition Users Guide User Manual

Page 268

background image

F

ACTORY

T

ALK

V

IEW

S

ITE

E

DITION

U

SER

S

G

UIDE

12–12

• •

Alarm priorities can be defined in an alarm server (Rockwell Automation Device Server

or Tag Alarm and Event Server), or in the FactoryTalk Directory.

If priority values are not defined in an alarm server, then the following system-wide

settings are in effect for all alarm servers in the FactoryTalk Directory.

You can change the range of severities associated with a given priority value.

If you change the settings held in the FactoryTalk Directory, the changes will apply to all

FactoryTalk alarm servers the directory manages. For more information, see “Setting up

system-wide alarm and event policies” on page 12-16.

If priority values are defined at an alarm server, the server-defined priorities take

precedence over the system-wide priorities.

You can set up server-defined priorities in the Properties dialog box for the Rockwell

Automation Device Server or Tag Alarm and Event Server. For details, see the

FactoryTalk Alarms and Events Help.

Alarm class

Use alarm classes to further group related alarms, based on characteristics other than

priority and severity.

For example, you might group alarms based on their function, to make it easier for

operators to identify alarms related to temperature, pressure, tank levels, equipment

running, or valves that fail to open or close.

To create an alarm class, in the Alarm and Event Setup editor, in any of the Digital, Level,

or Deviation Properties dialog boxes, type the class name in the Alarm class box, or select

one from the list of classes.

This priority value

Includes this range of severities

Urgent

751 to 1000

High

501 to 750

Medium

251 to 500

Low

1 to 250