12

Pla
ceho

lde

r

3. In the System Settings Properties dialog box (shown in the following illustration),

modify special events, event buffering, and alarm priority settings, as needed.

For details about options in the System Settings Properties dialog box, click Help.

To modify severity settings for system events

1. In FactoryTalk View Studio, in the Explorer window, expand the System, Policies,

System Policies, and FactoryTalk Alarms and Events folders.

2. Double-click Severity Settings.

3. In the Severity Settings Properties dialog box, modify the severity values associated

with selected system events.

For details about options in the Severity Settings Properties dialog box, click Help.

To modify the severity range for the alarm priorities, change the values in the Low boxes only.
Priorities defined at an alarm server override the system-wide settings held at the FactoryTalk
Directory.