Server Name” is unavailable. No strings for this
server were imported.

Server name associated with a string in the spreadsheet exists,
but the HMI server is not available. No strings associated with
this server will be imported.

The import will continue, but there will be no further attempts
to import strings and no further error messages logged, for this
server.

Server Name_Component Type_Component
Name
” does not exist in this application. No strings
for this component were imported.

Component name for a string in the spreadsheet does not exist
in the application. No strings associated with this component
name will be imported.

The import will continue, but there will be no further attempts
to import strings and no further error messages logged, for this
component name.

Server Name_Component Type_Component
Name_Description
” does not exist in this
application. No strings for this component were
imported.

Description for a string in the spreadsheet does not exist in the
application. No strings with this description will be imported.

The import will continue, but there will be no further attempts
to import strings and no further error messages logged, for this
description.

Optimized Duplicate String Reference” is pointing
to a string that does not exist in the spreadsheet. No
strings with this optimized duplicate string reference
were imported.

Optimized duplicate string reference in the spreadsheet refers to
a string that does not exist.

The import will continue, but there will be no further attempts
to import strings and no further error messages logged, for this
duplicate string reference.

Unable to save “Display Name.” No strings for this
component name were imported.

A graphic display or global object display cannot be saved. The
import will continue.

Unable to open “Display Name.” No strings for this
component name were imported.

A graphic display or global object display cannot be opened.
The import will continue.

Unable to import strings into “HMI Server Name” as
the currently logged in user doesn’t have write
access to the area.

The currently logged on user does not have FactoryTalk
Security Common Write access to the area containing the HMI
server whose strings are being imported.

Applies to FactoryTalk View SE network distributed
applications. No strings associated with this server will be
imported. However, the import will continue for any other HMI
servers in the application.

Unable to import strings as the currently logged in
user doesn’t have write access to the application.

The currently logged on user does not have Common Write
access to the application whose strings are being imported.
Applies to FactoryTalk View SE local station, network station,
and FactoryTalk View ME applications. No application strings
will be imported.