beautypg.com

Alarm acknowledgment, Alarm acknowledgment – 10 – Rockwell Automation FactoryTalk View Site Edition Users Guide User Manual

Page 222

background image

F

ACTORY

T

ALK

V

IEW

S

ITE

E

DITION

U

SER

S

G

UIDE

11–10

• •

Alarm system tags

System tags that provide HMI tag alarm status information are created and updated on the
HMI server. You can use these system tags wherever you can specify a tag name in
FactoryTalk View SE.

Alarm acknowledgment

An operator can acknowledge HMI tag alarms shown in an alarm summary or some other
HMI tag alarm display. Acknowledging an alarm does not correct the condition causing
the alarm, but indicates that the operator is aware of the alarm.

A tag, not an alarm, is acknowledged: a single tag might cause several alarms.

For example, a tag representing temperature might trigger Warm, Hot, and Overheat
alarms by the time it is acknowledged. The tag could also go in and out of alarm several
times before being acknowledged.

To display this alarm status information

Use this system tag

Of type

The most recent, most severe alarm. If an alarm of an equal
or higher severity occurs, it replaces the first alarm, whether
or not the previous alarm has been acknowledged.

system\AlarmBanner

String

The date of the most recent, most severe alarm.

system\AlarmMostRecentDate

String

The threshold label of the tag of the most recent, most
severe alarm.

system\AlarmMostRecentLabel

String

The severity of the most recent, most severe alarm.

system\AlarmMostRecentSeverity

Analog

The description of the tag of the most recent, most severe
alarm.

system\AlarmMostRecentTagDesc

String

The name of the tag of the most recent, most severe alarm.

system\AlarmMostRecentTagname

String

The time of the most recent, most severe alarm.

system\AlarmMostRecentTime

String

The units of the most recent, most severe alarm.

system\AlarmMostRecentUnits

String

The number of unacknowledged and suppressed alarms.

system\AlarmStatus

String

The number of alarm transactions in an unfiltered alarm
summary.

system\AlarmSummaryItems

Analog

The number of unacknowledged alarms in an unfiltered
alarm summary.

system\AlarmSummaryItemsUnacked

Analog

The number of tags with alarms suppressed.

system\AlarmSuppressedCount

Analog